Dry Type Distribution Transformer
We cover a wide range of Dry Type (VPI) Transformer with Off Circuit Tap Links / On Load Tap Changer (up to 2500 KVA in 11 KV Class.) conforming to the international standards of quality and safety for industries and commercial set-ups. These transformers are designed and developed using latest technologies and can be provided with a variety of terminations so as to suit the requirements for new installation or replacement.
RECON'S offer technologically advanced range Dry Type (VPI) Transformers using CRGO M3 to MS MOH Lamination, Electrolytic Grade 99.9% pure copper. These transformers are designed for trouble-free performance, confirming to IS - 2026 with low power loss and low noise. Use of modern manufacturing techniques and optimum utilization of active materials ensures cost effectiveness, reliability and a long trouble-free performance.
RECON'S Dry Type (VPI) Transformer are fitted in enclosure for Indoor installations and are totally maintenance free and safe from fire as the material used is metal, ceramic, NOMEX and resin. It is environment friendly as there is no oil, hence handling becomes easier and there are no chance of spillages and leakage and there is minimal nontoxic smoke in case of fire. Use of Class 'F' insulation increases the heat bearing capacity & enables the use of the transformer in humid and chemically polluted atmosphere also.
Applications :
Fire safety and environmental aspects are of increasing importance especially in respect of energy supply. The substitution of oil-filled transformers by dry type transformers is one of the most important step towards it. Dry Type transformer is used when it has to be located near load center and in a fire hazardous place. As there is no oil used in the transformer and special type of fire resistant insulation are used for the windings the fire risk is considerably reduced.
Standard Specifications
| Capacity | Up to 2500 KVA |
| No. of Phases | 3 Phase |
| Frequency | 50 Hz. |
| Voltage Range | 11 KV |
| Tapping | On Load Tap Changer to provide +5% to -15% Taps in steps of 1.25% on the H.T. Side. Else, Off Circuit Tap Links for ± 5% Taps on H.T. Side in steps of 2.5% each. |
| Insulation | Class 'F' (for Dry Type Trf.) |
| Vector Group | Dyn 11 |
| Duty Cycle | Continuous |
| Winding | Copper Wound |
| Terminals | As per required. |
Standard Fittings for Dry Type (VPI) Transformers
| Winding temperature Indicator | Cable Box on H.V. / L.V. Side. |
| Lifting lugs | Uni directional rollers |